System Sensor BEAM200 Reflected Beam Smoke Detectors

Fire Projects suggest System Sensor BEAM200 and BEAM200S single-ended reflected beam smoke detectors that are uniquely suited for protecting open areas with high ceilings where other methods of smoke detection are difficult to install and maintain. 
 
The System Sensor BEAM200 and BEAM200S installed by Fire Projects are intelligent reflected beam smoke detectors and designed to be used with UL Listed compatible control panels only. Since all of the wiring is connected to one side, the installation of the single-ended reflective design is much easier than dual-ended projected beam detectors. Alignment is accomplished quickly via an optical sight and a 2 digit signal strength meter incorporated into the product. Listed for operation from –22°F to 131°F, the System Sensor BEAM200 detector can be used in open area applications to provide early warning in environments where temperature extremes exceed the capability of other types of smoke detection.The System Sensor BEAM200 smoke detector supllied by Fire Projects, Ahmedabad includes one wired transmitter/ receiver unit and one reflector. When smoke enters the area between the unit and the reflector it causes a reduction in the signal. The alarm is activated when the smoke level reaches the predetermined threshold. System Sensor BEAM 200 and BEAM200s needs to installed qualified engineer.
 
The System Sensor BEAM200 device installed by Fire Projects has four standard sensitivity selections along with two Acclimate™ settings. When either of the two Acclimate settings are selected, the detector automatically adjusts its sensitivity using advanced software algorithms to select the optimum sensitivity for the specific environment.
 
The System Sensor BEAM200S model is equipped with an added feature, an integral sensitivity test feature that uses a test filter attached to a Servo motor  inside the detector optics. Using the remote test station RTS451/ RTS151, the motor is activated and moves the filter in the pathway of the light beam, thereby testing detector sensitivity. This integral sensitivity test feature allows the user to quickly and easily meet the S911 3017888 7260-1209:229 53-04-E 2165 annual maintenance and test requirements of NFPA 72.
 
Select Fire Projects for new implementation of System Sensor BEAM200 AND BEAM200S for advance level smoke detection and it is cost effective way for modern building, heritage sites with ornate ceiling. We support our clients from Designing up to Commissioning up to AMC. We also provide AMC–Annual Maintenance Contracts for all types of Fire & security Systems. 
 
Contact Fire Projects today to schedule your appointment with Fire Projects. Make call on number +91 9409535460.
 
• 16 to 328 foot protection range
• Single-ended, reflective design
• Easiest alignment in the industry with digital display
• 6 field selectable sensitivity levels
• Optional integral NFPA 72 sensitivity test feature
• Removable plug-in terminal blocks
• Built-in automatic gain control compensates for signal deterioration from dust build-up
• Remote test station available
• Paintable cover
• Optional heater kits available
  • Voltage 15 to 32 VDC
  • Avg. Standby Current: (24VDC) 2 mA Max
  • Avg. Current: During Testing 500 mA Max
  • Alarm Current:(24VDC) 8.5 mA Max
  • Fault Current: (24VDC) 4.5 mA Max
  • Alignment Mode Current: (24VDC) 20 mA Max
  • Current: 450 mA Max at 32 V (per reflector)
  • Power Consumption: 7.7 W at 24 V; 15 W at 32 V (per reflector)
  • Protection Range: 16 ft to 328 ft (5 m to 100 m)
  • Adjustment Angle: ±10 Degrees horizontal & vertical (The optics move independent of the unit)
  • Sensitivity Levels: Level 1 – 25%, Level 2 – 30%, Level 3 – 40%, Level 4 – 50%, Acclimate™ Level 1 – 30 to 50%, Acclimate Level 2 – 40 to 50%
  • Fault Condition (Trouble): 96% or more obscuration blockage In alignment mode Improper initial alignment Self-compensation limit reached
  • Alignment Aid: Optical gunsight, Integral signal strength indication, 2 digit display
  • Alarm Indicator: Local red LED and remote alarm
  • Trouble Indicator: Local yellow LED and remote trouble
  • Normal Indicator: Local flashing green LED
  • Test/Reset Features: Integral Sensitivity Test Filter (BEAM200S only, requires additional external power supply) Sensitivity filter (Incremental scale on reflector), Local test switch, Local reset switch, Remote test and reset switch (Compatible with RTS451 /RTS151 and RTS451KEY /RTS151 test station)
  • Smoke Detector Spacing:  On smooth ceilings, 30 to 60 feet between projected beams and not more than one-half that spacing between a projected beam and a sidewall. Other spacing may be used depending on ceiling height, airflow characteristics, and response requirements. See NFPA 72.
  • Temperature: –22°F to 131°F (–30°C to 55°C)
  • Humidity: 10 to 93% RH Noncondensing
  • Detector Dimensions: 10 in H × 7.5 in W × 3.3 in D (254 mm H × 191 mm W × 84 mm D)
  • Reflector Dimensions (16′ to 230′): 7.9 in × 9.1 in (200 mm × 230 mm)
  • Reflector Dimensions (beyond 230′): 15.7 in × 18.1 in (400 mm × 460 mm)